Arc Flash Report | Interstates

100 SWBD [MAIN SWBD] MAIN SWBD 3000 A 480 V 50 kASCR

CURRENT IN AMPERES

1

10

1000

1000

130 CB [PANEL 2] Frame/Rating 1200 A Sensor/Trip 1200 A Plug 1200A InterruptingRating 50 kA

Name 130 CB [PANEL 2] Data State Estimated Manufacturer SQUARE D Type PA Frame/Model PA

130 DCBL [PANEL 2] Non-Magnetic 350 kcmil 4-1/C+G QtyPerPhase 4 1.0 ft 130 CBL [PANEL 2] Non-Magnetic 350 kcmil 4-1/C+G QtyPerPhase 2 12.0 ft

Trip 1200.0 A Plug 1200.0 A Settings Phase

100

100

Thermal Curve INST HI (9120A)

Name 130 CB [BOILER RM PNL] Data State Estimated Manufacturer SQUARE D Type LA Frame/Model LA

130 PNL [PANEL 2] PANEL 2 1200 A 480 V 18 kASCR

10

10

Trip 400.0 A Plug 400.0 A Settings Recommended

130 CB [BOILER RM PNL] Frame/Rating 400A Sensor/Trip 400 A Plug 400A InterruptingRating 30 kA

Thermal Curve INST 2 (2564A)

130 CBL [BOILER RM PNL] Magnetic 350 kcmil 3-1/C+G QtyPerPhase 2 130.0 ft

Name 130 CB [AIR COMP 5] Data State Estimated Manufacturer SQUARE D Type KA Frame/Model KA

1

1

130 PNL [BOILER RM PNL] BOILER RM PNL

Trip 150.0 A Plug 150.0 A Settings Recommended

600 A 480 V 18 kASCR

Thermal Curve INST 2 (964.5A)

130 CB [AIR COMP 5] Frame/Rating 150A Sensor/Trip 150 A Plug 150A InterruptingRating 25 kA

0.10

0.10

ComponentName 130 MTR [AIR COMP 5] Rated HP 75.0 hp RatedAmps 90.5 A NumMotors 1

130 CBL[AIRCOMP5] Magnetic 1 AWG 3-1/C+G QtyPerPhase 1 110.0 ft

Group < 50hp 0 Load Adder 0.0 A

130ENC [AIR COMP5] AIR COMP 5

150 A 480 V 5 kASCR

0.01

0.01

130 MTR [AIR COMP5] 75 hp

NumMotors 1 Group < 50hp 0

TCCR 130-01 PANEL 2

Reference Voltage: 480 September 30, 2022

Base Project

SITE NAME ARC FLASH STUDY

Page 54 of 77

INTERSTATES DATE