Arc Flash Report | Interstates

100 SWBD [MAIN SWBD] MAIN SWBD 3000 A 480 V 50 kASCR

CURRENT IN AMPERES

1

10

1000

1000

130 CB [PANEL 2] Frame/Rating 1200A Sensor/Trip 1200A Plug 1200A InterruptingRating 50 kA

Name 130 CB [PANEL 2] Data State Estimated Manufacturer SQUARE D Type PA Frame/Model PA

130 DCBL [PANEL2] Non-Magnetic

350 kcmil 4-1/C+G QtyPerPhase 4 1.0 ft

100

100

Trip 1200.0 A Plug 1200.0 A Settings Phase

Thermal Curve INST HI (9120A)

130 CBL [PANEL2] Non-Magnetic

350 kcmil 4-1/C+G QtyPerPhase 2 12.0 ft

Name 130 CB [AMONIA UNIT 6] Data State Estimated Manufacturer SQUARE D Type LA Frame/Model LA

10

10

130 PNL [PANEL2] PANEL 2 1200 A 480 V 18 kASCR

Trip 400.0 A Plug 400.0 A Settings Phase

Thermal Curve INST HI (4000A)

130CB [AMONIAUNIT 6] Frame/Rating 400A Sensor/Trip 400A Plug 400A InterruptingRating 30 kA

1

1

130DCBL[AMONIAUNIT 6] Magnetic 3/0 AWG 3-1/C+G QtyPerPhase 2 0.1 ft

ComponentName 130 MTR [AMONIA UNIT 6] Rated HP 125.0 hp RatedAmps 150.8 A NumMotors 1

130CBL[AMONIAUNIT 6] Magnetic 3/0 AWG 3-1/C+G QtyPerPhase 1 100.0 ft

0.10

0.10

Group < 50hp 0 Load Adder 0.0 A

130ENC [AMONIAUNIT 6] AMONIAUNIT 6

250 A 480 V 10 kASCR

0.01

0.01

130MTR [AMONIAUNIT 6] 125 hp NumMotors 1 Group < 50hp 0

TCC 130-02 AMONIA UNIT 6

Reference Voltage: 480 September 30, 2022

Base Project

SITE NAME ARC FLASH STUDY

Page 55 of 77

INTERSTATES DATE

Powered by