100 SWBD [MAIN SWBD] MAIN SWBD 3000 A 480 V 50 kASCR
CURRENT IN AMPERES
1
10
1000
1000
130 CB [PANEL 2] Frame/Rating 1200 A Sensor/Trip 1200 A Plug 1200A InterruptingRating 50 kA
Name 130 CB [PANEL 2] Data State Estimated Manufacturer SQUARE D Type PA Frame/Model PA
130 DCBL [PANEL 2] Non-Magnetic 350 kcmil 4-1/C+G QtyPerPhase 4 1.0 ft 130 CBL [PANEL 2] Non-Magnetic 350 kcmil 4-1/C+G QtyPerPhase 2 12.0 ft
Trip 1200.0 A Plug 1200.0 A Settings Phase
100
100
Thermal Curve INST HI (9120A)
Name 130 CB [BOILER RM PNL] Data State Estimated Manufacturer SQUARE D Type LA Frame/Model LA
130 PNL [PANEL 2] PANEL 2 1200 A 480 V 18 kASCR
10
10
Trip 400.0 A Plug 400.0 A Settings Phase
130 CB [BOILER RM PNL] Frame/Rating 400A Sensor/Trip 400 A Plug 400A InterruptingRating 30 kA
Thermal Curve INST HI (4000A)
130 CBL [BOILER RM PNL] Magnetic 350 kcmil 3-1/C+G QtyPerPhase 2 130.0 ft
Name 130 CB [AIR COMP 5] Data State Estimated Manufacturer SQUARE D Type KA Frame/Model KA
1
1
130 PNL [BOILER RM PNL] BOILER RM PNL
Trip 150.0 A Plug 150.0 A Settings Phase
600 A 480 V 18 kASCR
Thermal Curve INST HI (1500A)
130 CB [AIR COMP 5] Frame/Rating 150A Sensor/Trip 150 A Plug 150A InterruptingRating 25 kA
0.10
0.10
ComponentName 130 MTR [AIR COMP 5] Rated HP 75.0 hp RatedAmps 90.5 A NumMotors 1
130 CBL[AIRCOMP5] Magnetic 1 AWG 3-1/C+G QtyPerPhase 1 110.0 ft
Group < 50hp 0 Load Adder 0.0 A
130ENC [AIR COMP5] AIR COMP 5
150 A 480 V 5 kASCR
0.01
0.01
130 MTR [AIR COMP5] 75 hp
NumMotors 1 Group < 50hp 0
TCC 130-01 PANEL 2
Reference Voltage: 480 September 30, 2022
Base Project
SITE NAME ARC FLASH STUDY
Page 53 of 77
INTERSTATES DATE
Powered by FlippingBook