Arc Flash Report | Interstates

100 SWBD [MAIN SWBD] MAIN SWBD 3000 A 480 V 50 kASCR

CURRENT IN AMPERES

1

10

1000

1000

11 0 CB [PANEL 1] Frame/Rating 1200 A Sensor/Trip 120 0 A Plug 1200 A InterruptingRating 50 kA

Name 110 CB [PANEL 1] Data State Estimated Manufacturer SQUARE D Type PA Frame/Model PA

110 DCBL[PANEL1] Non-Magnetic 350 kcmil 4-1/C+G QtyPerPhase 4 1.0 ft

100

100

Trip 1200.0 A Plug 1200.0 A Settings Phase

120 CBL[PANEL4] Non-Magnetic 350 kcmil 4-1/C+G QtyPerPhase 2 20.0 ft

Thermal Curve INST HI (9120A)

120 PNL[PANEL4] PANEL 4

600 A 480 V 18 kASCR

10

10

Name 120 CB [MCC IN SHOP] Data State Complete Manufacturer SQUARE D Type FA Frame/Model FA

120 CB [MCC IN SHOP] Frame/Rating 100 A Sensor/Trip 100 A Plug 100 A InterruptingRating 18 kA

Trip 100.0 A Plug 100.0 A Settings Phase Fixed

120 CBL[MCCIN SHOP] Magnetic 1/0 AWG 3-1/C+G QtyPerPhase 1 200.0 ft

1

1

120 MCC [MCC IN SHOP] MCC IN SHOP

600 A 480 V 42 kASCR

0.10

0.10

120 FUSE [BLAST FREEZERS] Frame/Rating 60 A Sensor/Trip 60 A InterruptingRating 200 kA

Name 120 FUSE [BLAST FREEZERS] Data State Complete Manufacturer LITTELFUSE Type FLSR, 600V RK5 Frame/Model FLSR Trip 60.0 A

120 CBL [BLAST FREEZE RS] Magnetic 6 AWG 3-1/C+G QtyPerPhase 1 75.0 ft

0.01

0.01

120 ENC [BLAST FREEZERS] BLAST FREEZERS 60 A 480 V 10 kASCR

TCC 120-0 4 MCC IN SHOP

Reference Voltage: 480 September 30, 2022

Base Project

SITE NAME ARC FLASH STUDY

Page 52 of 77

INTERSTATES DATE

Powered by