Arc Flash Report | Interstates

120 PNL [PANEL 4] PANEL 4

CURRENT IN AMPERES

600 A 480 V 18 kASCR

1

10

1000

1000

120 XFMR [MAINT SHOP XFMR]

120 CB [MAINT PNL A] Frame/Rating 150 A Sensor/Tr ip150A Plug 150A InterruptingRating 25 kA

Name 120 CB [MAINT PNL A] Data State Estimated Manufacturer SQUARE D Type KA Frame/Model KA

120 CBL [MAI NT PNL A] Magnetic 1/0 AWG 3-1/C+G QtyPerPhase 1 175.0 ft

Trip 150.0 A Plug 150.0 A Settings Phase

100

100

Thermal Curve INST HI (1500A)

120PNL [MAINTPNL A] MAINTENANCE PNLA

225 A 480 V 14 kASCR

120CBL [MAINT SHOPPNL D] Magnetic 1/0 AWG 3-1/C+G QtyPerPhase 1 175.0 ft

Name 120 CB [MAINT SHOP XFMR] Data State Complete Manufacturer SQUARE D Type FA Frame/Model FA

10

10

120PNL [MAINTSHOPPNL D] MAINTENANCE PNL D

600 A 480 V 18 kASCR

Trip 100.0 A Plug 100.0 A Settings Phase Fixed

120 CB [MAINT SHOP XFMR] Frame/Rating 100 A Sensor/Tr ip100A Plug 100A InterruptingRating 18 kA

1

1

120 XFMR [MAINT SHOP XFMR] Nominal kVA 75.0 kVA Z% 5.5000 %

120CBL [MAINT SHOPXFMR] Magnetic 2 AWG 3-1/C+G QtyPerPhase 1 5.0 ft

P

120 XFMR [MAINT SHOP XFMR] 75 kVA

S

480 V 208 V Z% 5.50 %

TX Inrush

0.10

0.10

Name 120 MCB [MAINT SHOP PNL B] Data State Complete Manufacturer CUTLER-HAMMER Type CA Frame/Model CA

120CBL [MAINT SHOPPNL B] Magnetic 1 AWG 4-1/C+G QtyPerPhase 1 5.0 ft

Trip 125.0 A Plug 125.0 A Settings Phase Fixed

120PNL [MAINTSHOPPNL B] MAINT SHOPPNL B

125 A 208 V 10 kASCR

0.01

0.01

120 MCB [MAINT SHOP PNL B] Frame/Rating 225 A Sensor/Tr ip125A Plug 125A InterruptingRating 10 kA

TCC 120-03 MAINT PNL A

Reference Voltage: 480 September 30, 2022

Base Project

SITE NAME ARC FLASH STUDY

Page 51 of 77

INTERSTATES DATE

Powered by