CURRENT IN AMPERES
1
10
1000
1000
100 SWBD [MAIN SWBD] MAIN SWBD 3000 A 480 V 50 kASCR
Name 110 CB [PANEL 1] Data State Estimated Manufacturer SQUARE D Type PA Frame/Model PA
110 CB [PANEL1] Frame/Rating 1200A Sensor/Trip 1200A Plug 1200A InterruptingRating 50 kA
100
100
Trip 1200.0 A Plug 1200.0 A Settings Phase
110 DCBL[PANEL 1] Non-Magnetic
Thermal Curve INST HI (9120A)
350 kcmil 4-1/C+G QtyPerPhase 4 1.0 ft
10
10
120 CBL [PANEL4] Non-Magnetic
350 kcmil 4-1/C+G QtyPerPhase 2 20.0 ft
120 PNL [PANEL4] PANEL 4
600 A 480 V 18 kASCR
Name 120 CB [AMFEC] Data State Estimated Manufacturer SQUARE D Type J-Frame, Powerpact Frame/Model JG
1
1
Trip 200.0 A Plug 200.0 A Settings Phase
120 CB [AMFEC] Frame/Rating 250A Sensor/Trip 200A Plug 200A InterruptingRating 35 kA
Thermal Curve INST (5-10 x Trip) High (2000A)
120 CBL [AMFEC] Magnetic 1/0 AWG 3-1/C+G QtyPerPhase 1 250.0 ft
0.10
0.10
120 ENC [AMFEC] AMFEC
150 A 480 V 10 kASCR
0.01
0.01
TCC 120-02 AMFEC
Reference Voltage: 480 September 30, 2022
Base Project
SITE NAME ARC FLASH STUDY
Page 50 of 77
INTERSTATES DATE
Powered by FlippingBook