Arc Flash Report | Interstates

CURRENT IN AMPERES

1

10

1000

1000

100 SWBD [MAIN SWBD] MAIN SWBD 3000 A 480 V 50 kASCR

Name 110 CB [PANEL 1] Data State Estimated Manufacturer SQUARE D Type PA Frame/Model PA

110 CB [PANEL1] Frame/Rating 1200A Sensor/Trip 1200A Plug 1200A InterruptingRating 50 kA

100

100

Trip 1200.0 A Plug 1200.0 A Settings Phase

110 DCBL[PANEL 1] Non-Magnetic

Thermal Curve INST HI (9120A)

350 kcmil 4-1/C+G QtyPerPhase 4 1.0 ft

10

10

120 CBL [PANEL4] Non-Magnetic

350 kcmil 4-1/C+G QtyPerPhase 2 20.0 ft

120 PNL [PANEL4] PANEL 4

600 A 480 V 18 kASCR

Name 120 CB [AMFEC] Data State Estimated Manufacturer SQUARE D Type J-Frame, Powerpact Frame/Model JG

1

1

Trip 200.0 A Plug 200.0 A Settings Phase

120 CB [AMFEC] Frame/Rating 250A Sensor/Trip 200A Plug 200A InterruptingRating 35 kA

Thermal Curve INST (5-10 x Trip) High (2000A)

120 CBL [AMFEC] Magnetic 1/0 AWG 3-1/C+G QtyPerPhase 1 250.0 ft

0.10

0.10

120 ENC [AMFEC] AMFEC

150 A 480 V 10 kASCR

0.01

0.01

TCC 120-02 AMFEC

Reference Voltage: 480 September 30, 2022

Base Project

SITE NAME ARC FLASH STUDY

Page 50 of 77

INTERSTATES DATE

Powered by