Arc Flash Report | Interstates

100 SWBD [MAIN SWBD] MAIN SWBD 3000 A 480 V 50 kASCR

CURRENT IN AMPERES

1

10

1000

1000

100 PNL [PANEL ABC XFMR]

100 CB [REFRIGERATION MCC] Frame/Rating 1000A Sensor/Trip 1000A Plug 1000A InterruptingRating 50 kA

Name 100 CB [REFRIGERATION MCC] Data State Estimated Manufacturer SQUARE D Type PA Frame/Model PA

Trip 1000.0 A Plug 1000.0 A Settings Phase

100 CBL [REFRIGERATION MCC] Non-Magnetic

350 kcmil 4-1/C+G QtyPerPhase 4 60.0 ft

100

100

Thermal Curve INST HI (9000A)

100 MCC [REFRIGERATION MCC] REFRIGERATION MCC 1200 A 480 V 22 kASCR

Name 100 CB [PANEL ABC XFMR] Data State Estimated Manufacturer CUTLER-HAMMER Type EGB, 3-4 Poles Frame/Model EGB

Trip 110.0 A Plug 110.0 A Settings Phase

10

10

100 CB [PANELABC XFMR] Frame/Rating 110A Sensor/Trip 110 A Plug 110A InterruptingRating 18 kA

Thermal Curve Magnetic (Fixed) Fixed (1155A)

100 PNL [PANEL ABC XFMR] Nominal kVA 75.0 kVA Z% 5.0000 %

100 CBL [PANELABC XFMR] Magnetic 2 AWG 3-1/C+G QtyPerPhase 1 45.0 ft

1

1

P

100 PNL[PANELABC XFMR] 75 kVA

S

480 V 240 V Z% 5.00 %

Name 100 MCB [PANEL B] Data State Complete Manufacturer CUTLER-HAMMER Type CA Frame/Model CA

TX Inrush

Trip 150.0 A Plug 150.0 A Settings Phase Fixed

100 CBL [PANELB] Magnetic 1 AWG 3-1/C+G QtyPerPhase 1 20.0 ft

0.10

0.10

100PNL[PANELB] PANEL B

150 A 240 V 10 kASCR

0.01

0.01

100 MCB [PANEL B] Frame/Rating 225A Sensor/Trip 150A Plug 150A InterruptingRating 10 kA

TCC 100-02 PANEL B

Reference Voltage: 480 September 30, 2022

Base Project

SITE NAME ARC FLASH STUDY

Page 47 of 77

INTERSTATES DATE

Powered by