100 SWBD [MAIN SWBD] MAIN SWBD 3000 A 480 V 50 kASCR
CURRENT IN AMPERES
1
10
1000
1000
110 CB [PANEL1] Frame/Rating 1200A Sensor/Trip 1200 A Plug 1200A InterruptingRating 50 kA
Name 110 CB [PANEL 1] Data State Estimated Manufacturer SQUARE D Type PA Frame/Model PA
110 DCBL [PANEL 1] Non-Magnetic 350 kcmil 4-1/C+G QtyPerPhase 4 1.0 ft
Trip 1200.0 A Plug 1200.0 A Settings Phase
100
100
110 CBL [PANEL 1] Non-Magnetic 350 kcmil 4-1/C+G QtyPerPhase 2 10.0 ft
Thermal Curve INST HI (9120A)
110 PNL [PANEL 1] PANEL 1 1200 A 480 V 18 kASCR
110 CB [CHILLROOMPNL] Frame/Rating 400A Sensor/Trip 400 A Plug 400A InterruptingRating 30 kA
10
10
Name 110 CB [CHILL ROOM PNL] Data State Estimated Manufacturer SQUARE D Type LA Frame/Model LA
110 CBL [CHILL ROOM PNL] Magnetic 500 kcmil 3-1/C+G QtyPerPhase 1 125.0 ft
Trip 400.0 A Plug 400.0 A Settings Phase
110 PNL[CHILLROOM PNL] CHILL ROOM PNL
Thermal Curve INST HI (4000A)
1
1
600 A 480 V 18 kASCR
Name 110 CB [PUMP CHILL H20 VFD] Data State Complete Manufacturer SQUARE D Type FA Frame/Model FA
110 CB [PUMP CHILL H20 VFD] Frame/Rating 100A Sensor/Trip 100 A Plug 100A InterruptingRating 18 kA
Trip 100.0 A Plug 100.0 A Settings Phase Fixed
110 CBL [PUMP CHILL H20 VFD] Magnetic 2 AW G 3-1/C+G QtyPerPhase 1 35.0 ft
0.10
0.10
110 ENC [PUMPCHILLH20VFD] PUMP CHILL H20 VFD
ComponentName 110 MTR [PUMP CHILL H20 VFD] Rated HP 25.0 hp RatedAmps 30.2 A NumMotors 1
100 A 480 V 5 kASCR
Group < 50hp 0 Load Adder 0.0 A
110 VFD [PUMPCHILLH20VFD]
0.01
0.01
110 MT R[PUMPCHILL H20 VFD] 25 hp NumMotors 1 Group < 50hp 0
TCC 110-01 PANEL 1
Reference Voltage: 480 September 30, 2022
Base Project
SITE NAME ARC FLASH STUDY
Page 48 of 77