CURRENT IN AMPERES
1
10
1000
1000
100 SWBD [MAIN SWBD] MAIN SWBD 3000 A 480 V 50 kASCR
Name 100 CB [REFRIGERATION MCC] Data State Estimated Manufacturer SQUARE D Type PA Frame/Model PA
100 CB [REFRIGERATION MCC] Frame/Rating 1000 A Sensor/Trip 1000 A Plug 1000 A InterruptingRating 50 kA
100
100
Trip 1000.0 A Plug 1000.0 A Settings Phase
Thermal Curve INST HI (9000A)
100 CBL [REFRIGERATION MCC] Non-Magnetic 350 kcmil 4-1/C+G QtyPerPhase 4 60.0 ft
Name 100 CB [300HP FES COMP] Data State Complete Manufacturer SIEMENS
10
10
100 MCC [REFRIGERATION MCC] REFRIGERATION MCC 1200 A 480 V 22 kASCR
Type HLXD6 Sentron Frame/Model HLXD6
Trip 600.0 A Plug 600.0 A Settings Phase
Thermal Curve (Fixed) INST (LO-HI) 2 (3430A)
100 CBL [300HPFES COMP] Magnetic 4/0 AWG 3-1/C+G QtyPerPhase 2 50.0 ft
1
1
100 ENC [300HP FES COMP] 300HP FES COMPRESSOR
600 A 480 V 35 kASCR
ComponentName 100 MTR [300HP FES COMP] Rated HP 300.0 hp RatedAmps 361.8 A NumMotors 1
100 CB [300HP FES COMP] Frame/Rating 600 A Sensor/Trip 600 A Plug 600 A InterruptingRating 65 kA
0.10
0.10
Group < 50hp 0 Load Adder 0.0 A
100 MTR [300HP FES COMP] 300 hp NumMotors 1 Group < 50hp 0
0.01
0.01
TCC 100-01 REFRIGERATION MCC
Reference Voltage: 480 September 30, 2022
Base Project
SITE NAME ARC FLASH STUDY
Page 46 of 77
INTERSTATES DATE
Powered by FlippingBook