100-01 MAIN SWBD
120-02 PANEL4 CONT
120 PNL [PANEL4] PANEL 4
600 A 480 V 18 kASCR
120 CB [N. POLAR] Frame/Rating 80 A Sensor/Trip 80A Plug 80 A InterruptingRating 18 kA
120 CB [MCC IN SHOP] Frame/Rating 100A Sensor/Tr ip 100 A Plug 100A InterruptingRating 18 kA
120 CB [WIELER GRNDR] Frame/Rating 100A Sensor/Trip 100 A Plug 100A InterruptingRating 18 kA
120 CB [AMMONIA COMP #4] Frame/Rating 250A Sensor/Trip 200 A Plug 200A InterruptingRating 25 kA
120 CB [AMMONIA COMP #8] Frame/Rating 250A Sensor/Tr ip 200 A Plug 200A InterruptingRating 25 kA
120 CB [EMULSIFIER DUMP] Frame/Rating 30 A Sensor/Trip 30A Plug 30 A InterruptingRating 18 kA
120 CB [VAC RM MCC] Frame/Rating 250A Sensor/Trip 200 A Plug 200A InterruptingRating 25 kA
120 CB [HONEY LIFT] Frame/Rating 20 A Sensor/Tr ip 20A Plug 20 A InterruptingRating 18 kA
120 CB [OPTI HYD PMP] Frame/Rating 100A Sensor/Trip 100 A Plug 100A InterruptingRating 25 kA
120 CB [MAINT PNLA] Frame/Rating 150A Sensor/Trip 150 A Plug 150A InterruptingRating 25 kA
120CBL[N. POLAR] Magnetic 4 AWG 3-1/C+G QtyPerPhase 1 200.0 ft
120 CBL [MCC IN SH OP] Magnetic 1/0 AWG 3-1/C+G QtyPerPhase 1 200.0 ft
120 CBL [WIELER GRNDR] Magnetic 2 AWG 3-1/C+G QtyPerPhase 1 25.0 ft
120 CBL[AMMONIA COMP#4] Magnetic 3/0 AWG 3-1/C+G QtyPerPhase 1 60.0 ft
120 CBL [AMMONIA COMP#8] Magnetic 3/0 AWG 3-1/C+G QtyPerPhase 1 55.0 ft
120 CBL [EMULSIFIER DUMP] Magnetic 10 AWG 3-1/C+G QtyPerPhase 1 25.0 ft
120 CBL[VAC RM MCC] Magnetic 3/0 AWG 3-1/C+G QtyPerPhase 1 100.0 ft
120 CBL [HON EY LIFT] Magnetic 12 AWG 3-1/C+G QtyPerPhase 1 150.0 ft
120 CBL [OPTI HYD PMP] Magnetic 2 AWG 3-1/C+G QtyPerPhase 1 30.0 ft
120 CBL [MAINT PNLA] Magnetic 1/0 AWG 3-1/C+G QtyPerPhase 1 175.0 ft
120 ENC [N. POLAR] N. POLAR 80 A 480 V 10 kASCR
120 ENC [WIELER GRNDR] EMULSIFER WIELER GRNDR
120ENC[AMMONIACOMP #4] AMMONIACOMP #4
120 ENC [AMMONIA COMP #8] AMMONIACOMP #8
120 ENC [EMULSIFIER DUMP] EMULSIFIER DUMP 30 A 480 V 5 kASCR
120 MCC [VAC RM MCC] VAC RM MCC
120 ENC [HONEY LIFT] HONEY LIFT 20 A 480 V 5 kASCR
120 ENC [OPTI HYD PMP] OPTI HYD PMP
100 A 480 V 5 kASCR
250 A 480 V 10 kASCR
250 A 480 V 10 kASCR
600 A 480 V 42 kASCR
100 A 480 V 5 kASCR
120 MCC [MCC IN SHOP] MCC IN SHOP
120 MTR [AMMONIACOMP#4] 75 hp NumMotors 1 Group < 50hp 0
120MTR[AMMONIACOMP#8] 75 hp NumMotors 1 Group < 50hp 0
120 PNL [MAINT PNLA] MAINTENANCEPNLA
600 A 480 V 42 kASCR
225 A 480 V 14 kASCR
120 FUSE [WEST MULEXFMR] Frame/Rating 40 A Sensor/Trip 40A InterruptingRating 200 kA
120 FUSE [EAST MULE XFMR] Frame/Rating 40 A Sensor/Tr ip 40A InterruptingRating 200 kA
120 FUSE [BLAST FREEZERS] Frame/Rating 60 A Sensor/Trip 60A InterruptingRating 200 kA
120 CB [DRY STORAGE BOX] Frame/Rating 30 A Sensor/Trip 30A Plug 30 A InterruptingRating 14 kA
120CBL[MAINT SHOP PNLD] Magnetic 1/0 AWG 3-1/C+G QtyPerPhase 1 175.0 ft
120 CBL[WEST MULE XFMR] Magnetic 8 AWG 3-1/C+G QtyPerPhase 1 60.0 ft
120 CBL [EAST MULE XFMR] Magnetic 8 AWG 3-1/C+G QtyPerPhase 1 100.0 ft
120 CBL [BLAST FREEZERS] Magnetic 6 AWG 3-1/C+G QtyPerPhase 1 75.0 ft
120 CBL [DRY STORAGE BOX] Magnetic 10 AWG 3-1/C+G QtyPerPhase 1 65.0 ft
120PNL[MAINT SHOP PNLD] MAINTENANCEPNLD
600 A 480 V 18 kASCR
P
P
120 XFMR [WEST MULE XFMR] 30 kVA
120 XFMR [EAST MULE XFMR] 30 kVA
120 ENC [BLAST FREEZERS] BLAST FREEZERS 60 A 480 V 10 kASCR
120 ENC [DRY STORAGE BOX] DRY STORAGE BOX FORMER 30 A 480 V 10 kASCR
120 CB [MAINT SHOP XFMR] Frame/Rating 100A Sensor/Trip 100 A Plug 100A InterruptingRating 18 kA
S
S
480 V 208 V Z% 4.60 %
480 V 208 V Z% 4.60 %
120CBL[WEST MULEPNL] Magnetic 1/0 AWG 4-1/C+G QtyPerPhase 1 5.0 ft
120 CBL [EAST MULE PNL] Magnetic 1/0 AWG 4-1/C+G QtyPerPhase 1 5.0 ft
120 CBL [MAINT SHOP XFMR] Magnetic 2 AWG 3-1/C+G QtyPerPhase 1 5.0 ft
P
120PNL[WEST MULEPNL] WEST MULE PNL
120 PNL [EAST MULE PNL LINE] EAST MULE PNL LI NE
120 XFMR [MAINT SHOP XFMR] 75 kVA
S
125 A 208 V 10 kASCR
125 A 208 V 10 kASCR
480 V 208 V Z% 5.50 %
120 MCB [WEST MULE PNL] Frame/Rating 225A Sensor/Trip 200 A Plug 200A InterruptingRating 100 kA
120 CB [EAST MULE PNL] Frame/Rating 225A Sensor/Tr ip 200 A Plug 200A InterruptingRating 100 kA
120 CBL [MAINT SHOP PNLC] Magnetic 1 AWG 4-1/C+G QtyPerPhase 1 5.0 ft
120 CBL [MAINT SHOP PNLB] Magnetic 1 AWG 4-1/C+G QtyPerPhase 1 5.0 ft
120 DCBL [EASTMU LE PNL] Magnetic 1/0 AWG 4-1/C+G QtyPerPhase 1 0.1 ft
120PNL[MAINT SHOP PNLC] MAINT SHOP PNLC
120PNL[MAINT SHOP PNLB] MAINT SHOP PNLB
100 A 208 V 10 kASCR
125 A 208 V 10 kASCR
120 PNL [EAST MULE PNL] EAST MULE PNL
120MCB [MAINT SHOP PNLB] Frame/Rating 225A Sensor/Trip 125 A Plug 125A InterruptingRating 10 kA
125 A 208 V 10 kASCR
120 CB [HAZMAT PNL] Frame/Rating 100A Sensor/Trip 60A Plug 60 A InterruptingRating 10 kA
120 CB [PACKOFF BRK RM PNL] Frame/Rating 100A Sensor/Tr ip 100 A Plug 100A InterruptingRating 10 kA
120 CBL[HAZMAT PNL] Magnetic 6 AWG 3-1/C+G QtyPerPhase 1 120.0 ft
120 CBL [PACKOFFBRK RM PNL] Magnetic 2 AWG 3-1/C+G QtyPerPhase 1 10.0 ft
120 PNL[HAZMAT PNL] HAZMAT PNL
120PNL[PACKOFFBRK RM PNL] PACKOFF BRK RM PNL
100 A 208 V 10 kASCR
100 A 208 V 10 kASCR
SMITHFIELD CARROLL, IA
120-01 PANEL 4
Base Project
ARC FLASH STUDY
October 4, 2022