Arc Flash Report | Interstates

100-01 MAIN SWBD

110 PNL[PANEL 1] PANEL 1 1200 A 480 V 18 kASCR

110 CB [POLAR MASSAGER S.] Frame/Rating 80A Sensor/Tr ip 80A Plug 80 A InterruptingRating 18 kA

110 CB [SEYDELMANN GRNDR] Frame/Rating 100A Sensor/Tr ip 100A Plug 100A InterruptingRating 18 kA

110 CB [PACK OFF CONV] Frame/Rating 15A Sensor/Tr ip 15A Plug 15 A InterruptingRating 18 kA

110 CB [CHILL ROOM PNL] Frame/Rating 400A Sensor/Tr ip 400A Plug 400A InterruptingRating 30 kA

110 CB [SPARE] Frame/Rating 150A Sensor/Tr ip 125A Plug 125A InterruptingRating 25 kA

110 CB [GRIND MIX/WIELER] Frame/Rating 150A Sensor/Tr ip 150A Plug 150A InterruptingRating 25 kA

110 CB [SUBWAY LINE] Frame/Rating 60A Sensor/Tr ip 60A Plug 60 A InterruptingRating 18 kA

110 CB [GRND/MIX HYD DUMP] Frame/Rating 40A Sensor/Tr ip 40A Plug 40 A InterruptingRating 18 kA

110 CB [XMFR MEZZ] Frame/Rating 100A Sensor/Tr ip 100A Plug 100A InterruptingRating 18 kA

110 CBL[POLAR MASSAGER S.] Magnetic 4 AWG 3-1/C+G QtyPerPhase 1 125.0 ft

110 CBL[SEYDELMANN GRNDR] Magnetic 2 AWG 3-1/C+G QtyPerPhase 1 120.0 ft

110CBL[PACKOFF CONV] Magnetic 12 AWG 3-1/C+G QtyPerPhase 1 350.0 ft

110 CBL[CHILL ROOM PNL] Magnetic 500 kcmil 3-1/C+G QtyPerPhase 1 125.0 ft

110 CBL[GRIND MIX/WIELER] Magnetic 1/0 AWG 3-1/C+G QtyPerPhase 1 25.0 ft

110 CBL[SUBWAY LINE] Magnetic 6 AWG 3-1/C+G QtyPerPhase 1 400.0 ft

110 CBL[GRND/MIX HYD DUMP] Magnetic 8 AWG 3-1/C+G QtyPerPhase 1 30.0 ft

110 CBL[XMFR MEZZ] Magnetic 2 AWG 3-1/C+G QtyPerPhase 1 175.0 ft

P

110 ENC [POLAR MASSAGER S.] 16000 POLAR MASSAGER S. 80 A 480 V 10 kASCR

110 ENC [SEYDELMANN GRNDR] SEYDELMANN GRNDR

110 ENC [PACK OFF CONV] PACK OFF CONV WEG DRIVE 15 A 480 V 5 kASCR

110 ENC [GRIND MIX/WIELER] GRINDING MIX/WIELER GRNDS

110 ENC [SUBWAY LINE] SUBWAY LINE 60 A 480 V 5 kASCR

110 ENC [GRND/MIX HYD DUMP] GRND/MIX HYD DUMP 40 A 480 V 5 kASCR

110 XFMR [XMFR MEZZ] 75 kVA

S

480 V 240 V Z% 5.00 %

100 A 480 V 10 kASCR

150 A 480 V 5 kASCR

SINGLE PHASE

110 PNL[CHILLROOM PNL] CHILLROOM PNL

110 CBL[BOILER RM LV PNL] Magnetic 3/0 AWG 3-1/C+G QtyPerPhase 1 15.0 ft

600 A 480 V 18 kASCR

110 CB [FLR LIFTHYD STR] Frame/Rating 30A Sensor/Tr ip 30A Plug 30 A InterruptingRating 18 kA

110 CB [CHILL H20 BILGE PMP] Frame/Rating 40A Sensor/Tr ip 40A Plug 40 A InterruptingRating 18 kA

110 CB [PUMP CHILL H20 VFD] Frame/Rating 100A Sensor/Tr ip 100A Plug 100A InterruptingRating 18 kA

110 CB [CHILLER RM XFMR] Frame/Rating 50A Sensor/Tr ip 50A Plug 50 A InterruptingRating 18 kA

110 CB [CHILL RM PMP STR] Frame/Rating 15A Sensor/Tr ip 15A Plug 15 A InterruptingRating 18 kA

110 CB [MARLEN PMP] Frame/Rating 60A Sensor/Tr ip 60A Plug 60 A InterruptingRating 18 kA

110 PNL[BOILER RM LV PNL] BOILER RM LV PNL

200 A 240 V 10 kASCR

110 CBL[FLR LIFT HYD STR] Magnetic 10 AWG 3-1/C+G QtyPerPhase 1 15.0 ft

110 CBL[CHILL H20 BILGE PMP] Magnetic 8 AWG 3-1/C+G QtyPerPhase 1 20.0 ft

110 CBL[PUMP CHILL H20VFD] Magnetic 2 AWG 3-1/C+G QtyPerPhase 1 35.0 ft

110 CBL[CHILLER RM XFMR] Magnetic 6 AWG 3-1/C+G QtyPerPhase 1 15.0 ft

110 CBL[CHILL RM PMP STR] Magnetic 12 AWG 3-1/C+G QtyPerPhase 1 20.0 ft

110 CBL[MARLEN PMP] Magnetic 6 AWG 3-1/C+G QtyPerPhase 1 60.0 ft

110 MCB [BOILER RM LV PNL] Frame/Rating 200A Sensor/Tr ip 200A Plug 200A InterruptingRating 35 kA

P

110 STR [FLR LIFTHYD STR] FLR LIFT HYD STR 30 A 480 V 5 kASCR

110 ENC [CHILLH20 BILGE PMP] CHILL H20 BILGE PMP 40 A 480 V 5 kASCR

110 ENC [PUMPCHILL H20 VFD ] PUMP CHILLH20 VFD

110 XFMR [CHILLER RM XFMR] 45 kVA

110 STR [CHILLRM PMP STR] CHILL RM PMP STR 20 A 480 V 5 kASCR

110 ENC [MARLEN PMP] MARLEN PMP 60 A 480 V 10 kASCR

S

100 A 480 V 5 kASCR

480 V 240 V Z% 5.00 %

SINGLE PHASE

110VFD [PUMP CHILLH20VFD]

110 CBL[CHILLER RM LV PNL] Magnetic 2 AWG 3-1/C+G QtyPerPhase 1 15.0 ft

110 MTR [PUMPCHILL H20 VFD] 25 hp

110 PNL[CHILLER RM LV PNL] CHILLER RM LV PNL

100 A 240 V 10 kASCR

NumMotors 1 Group < 50hp 0

SMITHFIELD CARROLL, IA

110-01 PANEL 1

Base Project

ARC FLASH STUDY

October 4, 2022

Powered by