100 UTIL[MAIN UTIL] 12470 V
SC Contribution3P3486.0 Amps SC ContributionSLG 2628.0 Amps
P
100 XFMR [MAIN XFMR] 1500 kVA 12470 V 480 V Z% 5.75 %
S
100 CBL[MAIN SWBD] Non-Magnetic
500 kcmil 4-1/C+G QtyPerPhase 8 50.0 ft
6-Switch Rule Service Disconnects Must Be Labeled Per NEC Requirements
100 SWBD [MAIN SWBD] MAIN SWBD 3000 A 480 V 50 kASCR
100 CBL[CAPDISC] Non-Magnetic
100 CB [REFRIGERATION MCC] Frame/Rating 1000 A Sensor/Trip 1000 A Plug 1000 A InterruptingRating 50 kA
110 CB[PANEL1] Frame/Rating 1200 A Sensor/Trip 1200 A Plug 1200 A InterruptingRating 50 kA
130 CB [PANEL2] Frame/Rating 1200 A Sensor/Trip 1200 A Plug 1200 A InterruptingRating 50 kA
3/0 AWG 4-1/C+G QtyPerPhase 1 10.0 ft
100 DISC [CAPDISC] CAP DISC
100 CBL[REFRIGERATION MCC] Non-Magnetic
110 DCBL[PANEL1] Non-Magnetic
130 DCBL[PANEL2] Non-Magnetic
200 A 480 V 100 kASCR
350 kcmil 4-1/C+G QtyPerPhase 4 60.0 ft
350 kcmil 4-1/C+G QtyPerPhase 4 1.0 ft
350 kcmil 4-1/C+G QtyPerPhase 4 1.0 ft
NEC VIOLATION
NEC VIOLATION
100 FUSE[CAPDISC] Frame/Rating 200 A Sensor/Trip 200 A InterruptingRating 200 kA
110 CBL[PANEL1] Non-Magnetic
120 CBL[PANEL4] Non-Magnetic
130 CBL[PANEL2] Non-Magnetic
140 CBL[PANEL3] Non-Magnetic
350 kcmil 4-1/C+G QtyPerPhase 2 10.0 ft
350 kcmil 4-1/C+G QtyPerPhase 2 20.0 ft
350 kcmil 4-1/C+G QtyPerPhase 2 12.0 ft
350 kcmil 4-1/C+G QtyPerPhase 2 15.0 ft
110 PNL[PANEL1] PANE L1 1200 A 480 V 18 kASCR
120 PNL[PANEL4] PANE L4
130 PNL[PANEL2] PANE L2 1200 A 480 V 18 kASCR
140 PNL[PANEL3] PANE L3
600 A 480 V 18 kASCR
800 A 480 V 18 kASCR
110-01 PANEL1
120-01 PANEL4
130-01 PANEL2
140-01 PANEL3
120-02 PANEL4 CONT
130-02 PANEL2 CONT
140-02 PANEL3 CONT
140-03 PANEL3 CONT(2)
100 MCC [REFRIGERATION MCC] REFRIGERATION MCC 1200 A 480 V 22 kASCR
100 CBL[CONDENSOR NO2 FANS] Magnetic 2 AWG 3-1/C+G QtyPerPhase 1 8.0 ft
100 CBL[N.ACCUMULATOR STR] Magnetic 2 AWG 3-1/C+G QtyPerPhase 1 5.0 ft
100 CB [PANELABC XFMR] Frame/Rating 110 A Sensor/Trip 110 A Plug 110 A InterruptingRating 18 kA
100 CBL[PANELF] Magnetic
100 CBL[S.ACCUMULATORSTR] Magnetic 2 AWG 3-1/C+G QtyPerPhase 1 5.0 ft
100 CBL[NO.3 CONDENSORSTR] Magnetic 2 AWG 3-1/C+G QtyPerPhase 1 5.0 ft
100 CBL[300HP FES COMP] Magnetic
4/0 AWG 4-1/C+G QtyPerPhase 1 15.0 ft
4/0 AWG 3-1/C+G QtyPerPhase 2 50.0 ft
100 ENC [CONDENSOR NO 2 FANS] CONDENSOR NO 2 FANS
100 STR [N.ACCUMULATOR STR] N.ACCUMULATORSTR
100 CBL[PANELABC XFMR] Magnetic 2 AWG 3-1/C+G QtyPerPhase 1 45.0 ft
100 STR [S. ACCUMULATOR STR] S.ACCUMULATORSTR
100 STR [NO. 3 CONDENSOR STR] NO. 3 CONDENSOR STR
100 ENC [300HP FES COMP] 300HP FES COMPRESSOR
100 A 480 V 10 kASCR
100 A 480 V 10 kASCR
100 A 480 V 10 kASCR
100 A 480 V 10 kASCR
600 A 480 V 35 kASCR
NEC VIOLATION
P
100 PNL[PANELABC XFMR] 75 kVA
100 PNL[PANELF] PANE LF
100 CB [300HPFESCOMP] Frame/Rating 600 A Sensor/Trip 600 A Plug 600 A InterruptingRating 65 kA
SINGLE PHASE
S
250 A 480 V 18 kASCR
480 V 240 V Z% 5.00 %
100 CBL[PANELA] Magnetic 1 AWG 3-1/C+G QtyPerPhase 1 20.0 ft
100 CBL[PANELB] Magnetic 1 AWG 3-1/C+G QtyPerPhase 1 20.0 ft
100 CBL[PANELC] Magnetic 1 AWG 3-1/C+G QtyPerPhase 1 20.0 ft
100 CB [INJECTOR #1 COOLING] Frame/Rating 15 A Sensor/Trip 15 A Plug 15 A InterruptingRating 18 kA
100 CB [PANELEXFMR] Frame/Rating 30 A Sensor/Trip 30 A Plug 30 A InterruptingRating 18 kA
100 MTR [300HP FES COMP] 300 hp NumMotors 1 Group < 50hp 0
100 PNL[PANELA] PANE LA
100 PNL[PANELB] PANE LB
100 PNL[PANELC] PANE LC
100 CBL[INJECTOR#1 COOLING] Magnetic 12 AWG 3-1/C+G QtyPerPhase 1 5.0 ft
100 CBL[PANELEXFMR] Magnetic 10 AWG 3-1/C+G QtyPerPhase 1 35.0 ft
150 A 240 V 10 kASCR
150 A 240 V 10 kASCR
150 A 240 V 10 kASCR
P
100 MCB[PANELA] Frame/Rating 225 A Sensor/Trip 150 A Plug 150 A InterruptingRating 10 kA
100 MCB [PANEL B] Frame/Rating 225 A Sensor/Trip 150 A Plug 150 A InterruptingRating 10 kA
100 ENC [INJECTOR #1 COOLING] INJECTORROOM#1 COOLING UNIT 30 A 480 V 5 kASCR
100 XFMR [PANEL E XFMR] 15 kVA
S
480 V 240 V Z% 6.00 %
100 CBL[PANELE] Magnetic 6 AWG 3-1/C+G QtyPerPhase 1 10.0 ft
100 PNL[PANELE] PANE LE
100 A 240 V 10 kASCR
100 MCB [PANEL E] Frame/Rating 60 A Sensor/Trip 60 A Plug 60 A InterruptingRating 10 kA
SMITHFIELD CARROLL, IA
100-01 MAIN SWBD
Base Project
ARC FLASH STUDY
October 4, 2022