120-01 PANEL 4
120 PNL [PANEL4] PANEL 4
600 A 480 V 18 kASCR
120CB [AMMONIACOMP #5VFD] Frame/Rating 250A Sensor/Trip 200A Plug 200A InterruptingRating 35 kA
120 CB [BOLDT MIXER] Frame/Rating 60A Sensor/Trip 60A Plug 60 A InterruptingRating 18 kA
120 CB [AMFEC] Frame/Rating 250A Sensor/Trip 200A Plug 200A InterruptingRating 35 kA
120 CB [N. POLAR DUMPER] Frame/Rating 30A Sensor/Trip 30A Plug 30 A InterruptingRating 65 kA
120CBL[AMMONIACOMP #5VFD] Magnetic 3/0 AWG 3-1/C+G QtyPerPhase 1 100.0 ft
120 CBL [BOLDT MIXER] Magnetic 6 AWG 3-1/C+G QtyPerPhase 1 50.0 ft
120 CBL [AMFEC] Magnetic 1/0 AWG 3-1/C+G QtyPerPhase 1 250.0 ft
120 CBL [N. POLAR DUMPER] Magnetic 10 AWG 3-1/C+G QtyPerPhase 1 200.0 ft
120ENC [AMMONIACOMP #5VFD] AMMONIACOMP #5VFD
120 ENC [BOLDT MIXER] BOLDT MIXER 60 A 480 V 10 kASCR
120 ENC [AMFEC] AMFEC
120 ENC [N. POLAR DUMPER] N. POLAR DUMPER 30 A 480 V 10 kASCR
250 A 480 V 10 kASCR
150 A 480 V 10 kASCR
120VFD [AMMONIACOMP #5VFD]
120 MTR [AMFEC] 50 hp NumMotors 1 Group < 50hp 0
120MTR [AMMONIACOMP #5VFD] 125 hp NumMotors 1 Group < 50hp 0
SMITHFIELD CARROLL, IA
120-02 PANEL 4 CONT
Base Project
ARC FLASH STUDY
October 4, 2022
Powered by FlippingBook