Arc Flash Report | Interstates

120-01 PANEL 4

120 PNL [PANEL4] PANEL 4

600 A 480 V 18 kASCR

120CB [AMMONIACOMP #5VFD] Frame/Rating 250A Sensor/Trip 200A Plug 200A InterruptingRating 35 kA

120 CB [BOLDT MIXER] Frame/Rating 60A Sensor/Trip 60A Plug 60 A InterruptingRating 18 kA

120 CB [AMFEC] Frame/Rating 250A Sensor/Trip 200A Plug 200A InterruptingRating 35 kA

120 CB [N. POLAR DUMPER] Frame/Rating 30A Sensor/Trip 30A Plug 30 A InterruptingRating 65 kA

120CBL[AMMONIACOMP #5VFD] Magnetic 3/0 AWG 3-1/C+G QtyPerPhase 1 100.0 ft

120 CBL [BOLDT MIXER] Magnetic 6 AWG 3-1/C+G QtyPerPhase 1 50.0 ft

120 CBL [AMFEC] Magnetic 1/0 AWG 3-1/C+G QtyPerPhase 1 250.0 ft

120 CBL [N. POLAR DUMPER] Magnetic 10 AWG 3-1/C+G QtyPerPhase 1 200.0 ft

120ENC [AMMONIACOMP #5VFD] AMMONIACOMP #5VFD

120 ENC [BOLDT MIXER] BOLDT MIXER 60 A 480 V 10 kASCR

120 ENC [AMFEC] AMFEC

120 ENC [N. POLAR DUMPER] N. POLAR DUMPER 30 A 480 V 10 kASCR

250 A 480 V 10 kASCR

150 A 480 V 10 kASCR

120VFD [AMMONIACOMP #5VFD]

120 MTR [AMFEC] 50 hp NumMotors 1 Group < 50hp 0

120MTR [AMMONIACOMP #5VFD] 125 hp NumMotors 1 Group < 50hp 0

SMITHFIELD CARROLL, IA

120-02 PANEL 4 CONT

Base Project

ARC FLASH STUDY

October 4, 2022

Powered by