Drawing E08-03 (Continued) Test Points
Area
Point
Equipment Tested P-483 (Above DC)
Test Value (Ohms)
Grounded Circuit Used
3rd Floor Compactor Area (Area 11) 3rd Floor Compactor Area (Area 11) 3rd Floor Compactor Area (Area 11) 3rd Floor Compactor Area (Area 11) 3rd Floor Compactor Area (Area 11) 3rd Floor Compactor Area (Area 11) 3rd Floor Compactor Area (Area 11) 3rd Floor Compactor Area (Area 11)
80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99
0.68 0.71 0.55 0.59 0.39 0.54 0.55 0.51 1.43 0.71 0.46 0.45 5.37 0.47 1.70 0.40 0.41 0.67 1.11 1.26 1.33
Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Panel #3 Recept, CB# N/A Panel #3 Recept, CB# N/A Panel #3 Recept, CB# N/A Panel #3 Recept, CB# N/A Panel #3 Recept, CB# N/A Panel #3 Recept, CB# N/A Panel #3 Recept, CB# N/A Panel #3 Recept, CB# N/A Panel #3 Recept, CB# N/A Panel #3 Recept, CB# N/A Panel #3 Recept, CB# N/A Panel #3 Recept, CB# N/A Panel #3 Recept, CB# N/A
DC Tank Elevator
Airline Tank 2 Tank 3
A Compactor
A Compactor Motor
Bulk Area (Area 17) Bulk Area (Area 17) Bulk Area (Area 17) Bulk Area (Area 17) Bulk Area (Area 17) Bulk Area (Area 17) Bulk Area (Area 17) Bulk Area (Area 17) Bulk Area (Area 17) Bulk Area (Area 17) Bulk Area (Area 17) Bulk Area (Area 17) Bulk Area (Area 17) Bulk Area (Area 17) Bulk Area (Area 17)
YPS Feeder
Mixing Screw
YPS Disconnect
Additive Feeder Disconnect
Dust Collector Tank Dust Collector Motor
Lighting Panel 1 Lighting Panel 2
XFMR
XFMR Disconnect
Dust Collector Disconnect
Outside Dust Collector
100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115
Outside Dust Tank
Vac Pan Silo Housing
N/A
Vac Pan Silo Tank
1.77
Maintenance Area (Area 20) Maintenance Area (Area 20) Maintenance Area (Area 20) Maintenance Area (Area 20) Maintenance Area (Area 20) Maintenance Area (Area 20) Maintenance Area (Area 20) Maintenance Area (Area 20) Maintenance Area (Area 20) Maintenance Area (Area 20) Maintenance Area (Area 20) Maintenance Area (Area 20) Maintenance Area (Area 20)
Panel D
0.36 0.51 0.27 0.27
Lighting XFMR Disconnect
Lighting Panel 4 Lighting Panel 2 Lighting Panel 3
N/A
Lighting XFMR
0.27 0.27 0.31 3.75 2.90
Switchgear
Maintenance Disconnect
Lighting Panel 1
Welding Disconnect 1
Welding Frame
1000.00
Welding Disconnect 2 Welding Disconnect 3
6.40 2.84
CLIENT NAME, FACILITY LOCATION GROUNDING REPORT
Page 12 of 23
INTERSTATES MONTH XX, XXXX
Powered by FlippingBook