CURRENT IN AMPERES

1

10

1000

1000

100 SWBD [MAIN SWBD] MAIN SWBD 3000 A 480 V 50 kASCR

130 CB [PANEL 2] Frame/Rating 1200A Sensor/Trip 1200A Plug 1200A InterruptingRating 50 kA

100

100

Name 130 CB [PANEL 2] Data State Estimated Manufacturer SQUARE D Type PA Frame/Model PA

130 DCBL [PANEL2] Non-Magnetic

350 kcmil 4-1/C+G QtyPerPhase 4 1.0 ft

Trip 1200.0 A Plug 1200.0 A Settings Phase

Thermal Curve INST HI (9120A)

10

10

140 CBL [PANEL3] Non-Magnetic

350 kcmil 4-1/C+G QtyPerPhase 2 15.0 ft

140 PNL [PANEL3] PANEL 3

800 A 480 V 18 kASCR

Name 140 CB [10000 MEPACO] Data State Estimated Manufacturer SQUARE D Type KA Frame/Model KA

1

1

Trip 200.0 A Plug 200.0 A Settings Recommended

140 CB [10000 MEPACO] Frame/Rating 250A Sensor/Trip 200A Plug 200A InterruptingRating 25 kA

Thermal Curve INST 3 (1362A)

140 CBL [10000 MEPACO] Magnetic 3/0 AWG 3-1/C+G QtyPerPhase 1 250.0 ft

0.10

0.10

140 ENC [10000 MEPACO] 10000 MEPACO

200 A 480 V 10 kASCR

0.01

0.01

TCCR 140-02 10000 MEPACO

Reference Voltage: 480 September 30, 2022

Base Project

SITE NAME ARC FLASH STUDY

Page 59 of 77

INTERSTATES DATE