CURRENT IN AMPERES
1
10
1000
1000
100 SWBD [MAIN SWBD] MAIN SWBD 3000 A 480 V 50 kASCR
130 CB [PANEL 2] Frame/Rating 1200A Sensor/Trip 1200A Plug 1200A InterruptingRating 50 kA
100
100
Name 130 CB [PANEL 2] Data State Estimated Manufacturer SQUARE D Type PA Frame/Model PA
130 DCBL [PANEL2] Non-Magnetic
350 kcmil 4-1/C+G QtyPerPhase 4 1.0 ft
Trip 1200.0 A Plug 1200.0 A Settings Phase
Thermal Curve INST HI (9120A)
10
10
140 CBL [PANEL3] Non-Magnetic
350 kcmil 4-1/C+G QtyPerPhase 2 15.0 ft
140 PNL [PANEL3] PANEL 3
800 A 480 V 18 kASCR
Name 140 CB [10000 MEPACO] Data State Estimated Manufacturer SQUARE D Type KA Frame/Model KA
1
1
Trip 200.0 A Plug 200.0 A Settings Phase
140 CB [10000 MEPACO] Frame/Rating 250A Sensor/Trip 200A Plug 200A InterruptingRating 25 kA
Thermal Curve INST HI (2000A)
140 CBL [10000 MEPACO] Magnetic 3/0 AWG 3-1/C+G QtyPerPhase 1 250.0 ft
0.10
0.10
140 ENC [10000 MEPACO] 10000 MEPACO
200 A 480 V 10 kASCR
0.01
0.01
TCC 140-02 10000 MEPACO
Reference Voltage: 480 September 30, 2022
Base Project
SITE NAME ARC FLASH STUDY
Page 58 of 77
INTERSTATES DATE
Powered by FlippingBook