Grounding Audit Report | Interstates

Drawing E08-02 Test Points

Area

Point

Equipment Tested

Test Value (Ohms)

Grounded Circuit Used

Pellet DC MCC Room (Area 4) Pellet DC MCC Room (Area 4) Pellet DC MCC Room (Area 4) Pellet DC MCC Room (Area 4) Pellet DC MCC Room (Area 4) Pellet DC MCC Room (Area 4) Pellet DC MCC Room (Area 4) Pellet DC MCC Room (Area 4) Pellet DC MCC Room (Area 4) Pellet DC MCC Room (Area 4) Pellet DC MCC Room (Area 4) Pellet DC MCC Room (Area 4) Pellet DC MCC Room (Area 4) Pellet DC MCC Room (Area 4) Bulk MCC Room (Area 5) Bulk MCC Room (Area 5) Bulk MCC Room (Area 5) Bulk MCC Room (Area 5) Bulk MCC Room (Area 5) Bulk MCC Room (Area 5) Bulk MCC Room (Area 5) Bulk MCC Room (Area 5) Micro MCC Room (Area 6) Micro MCC Room (Area 6) Micro MCC Room (Area 6) Micro MCC Room (Area 6) Roundcan MCC Room (Area 7) Roundcan MCC Room (Area 7) Roundcan MCC Room (Area 7) Roundcan MCC Room (Area 7)

1 2 3 4 5 6 7 8 9

DC MCC Room Air Conditioner

0.34 0.30 0.65 0.36 0.40 0.42 0.34 0.39 0.32 0.36 0.33 0.37 0.55 0.46 0.36 0.41 0.35 0.35 0.44 0.68 0.42 0.34

Recept by Air Conditioner, CB# N/A Recept by Air Conditioner, CB# N/A Recept by Air Conditioner, CB# N/A Recept by Air Conditioner, CB# N/A Recept by Air Conditioner, CB# N/A Recept by Air Conditioner, CB# N/A Recept by Air Conditioner, CB# N/A Recept by Air Conditioner, CB# N/A Recept by Air Conditioner, CB# N/A Recept by Air Conditioner, CB# N/A Recept by Air Conditioner, CB# N/A Recept by Air Conditioner, CB# N/A Recept by Air Conditioner, CB# N/A Recept by Air Conditioner, CB# N/A Recept for Emergency Light, CB# N/A Recept for Emergency Light, CB# N/A Recept for Emergency Light, CB# N/A Recept for Emergency Light, CB# N/A Recept for Emergency Light, CB# N/A Recept for Emergency Light, CB# N/A Recept for Emergency Light, CB# N/A Recept for Emergency Light, CB# N/A

PLC P-0

MCC 1CA

Lighting Panel M

MCC 2D

Lighting Panel 1CA XFMR

DC MCC Mains Feed

XFMR 1CA XFMR 1CB

10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

Lighting Panel Sub-S

PLC M-0 MCC 2H MCC 1CB

Eriez Control Panel

PLC R-1

PLC M-1 PLC P-1 PLC Q-0

Bulk MCC Room Air Conditioner

MCC 1M

Pellet Bin Vibratory Conveyor Panel

Communication Node Panel

Micro MCC

0.97 1.09

Closest Recept in Micro MCC Room, CB# N/A Closest Recept in Micro MCC Room, CB# N/A Closest Recept in Micro MCC Room, CB# N/A Closest Recept in Micro MCC Room, CB# N/A Recept on Column Outside Room, CB# N/A Recept on Column Outside Room, CB# N/A Recept on Column Outside Room, CB# N/A Recept on Column Outside Room, CB# N/A

Micro A/C Disconnect

Micro A/C Blower

22.00*

Micro A/C Condenser

1.36

Roundcan MCC Room Air Conditioner

4.70 3.50 3.50 3.55

MCC 1H

Old Dairymill MCC Main

RMCC Data Cabinet

Grain MCC Room (Area 8)

N/A

Equipment in this area is being demoed

N/A

N/A

Battery Charger MCC Room (Area 9) Battery Charger MCC Room (Area 9)

31 32

MCC 2F

2.10 1.86

Unknown Panel, CB# N/A Unknown Panel, CB# N/A

110 Panel

*Original Ohm reading is showing for point 25. Corrective actions have been completed for this item, but an updated Ohm reading wasn't provided.

CLIENT NAME, FACILITY LOCATION GROUNDING REPORT

Page 9 of 23

INTERSTATES MONTH XX, XXXX

Powered by