Drawing E08-04 (Continued) Test Points
Area
Point
Equipment Tested A-2A Lighting Panel
Test Value (Ohms)
Grounded Circuit Used
Boiler House Area (Area 15) Boiler House Area (Area 15) Boiler House Area (Area 15) Boiler House Area (Area 15) Boiler House Area (Area 15) Boiler House Area (Area 15) Boiler House Area (Area 15) Boiler House Area (Area 15) Boiler House Area (Area 15) Boiler House Area (Area 15) Boiler House Area (Area 15) Boiler House Area (Area 15) Boiler House Area (Area 15) Boiler House Area (Area 15) Boiler House Area (Area 15) Boiler House Area (Area 15)
56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90
0.34 0.30 0.26 0.32 0.40 0.83 0.28 0.50 0.29 0.50 0.30 0.38 0.28 0.44 0.32 0.33
A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A
A2 Lighting Panel
XFMR
Lighting Panel A-1
Junction Box
XFMR
Boiler Fan Decay
Water Lines (Pipes)
Weld Receptacle
Boiler Fan Disconnect
Boiler Fan Motor
PLC Cabinet
Monitoring Solutions
XFMR
Tank
Valves
Cooling Area (Area 16) Cooling Area (Area 16) Cooling Area (Area 16) Vac Pan Area (Area 18) Vac Pan Area (Area 18) Vac Pan Area (Area 18) Vac Pan Area (Area 18) Vac Pan Area (Area 18) Vac Pan Area (Area 18) Vac Pan Area (Area 18) Vac Pan Area (Area 18) Vac Pan Area (Area 18) Vac Pan Area (Area 18) Vac Pan Area (Area 18) Vac Pan Area (Area 18) Vac Pan Area (Area 18) Vac Pan Area (Area 18) Vac Pan Area (Area 18) Vac Pan Area (Area 18)
50K Tank 50K Tank 50K Tank
0.41
N/A N/A N/A
119.00 365.00
Reclaim Pump Motor
0.49 0.67 0.39 0.49 1.71 0.30 0.32 0.35 0.27 0.58 0.27 2.10 0.47 9.50 1.36 1.41
Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A
Reclaim Pump Disconnect Condensate Pressure Pump
Vac Pump
#4 Purge Pump
#4 Exhauster Motor
#4 Condensate Motor Evaporator Feed Motor
#3 Exhauster #2 Exhauster #1 Exhauster
Slurry Pump Motor
Screw Motor
Filter Wheel Motor
3rd Floor Lighting Panel 1 3rd Floor Lighting Panel 2
CLIENT NAME, FACILITY LOCATION GROUNDING REPORT
Page 14 of 23
INTERSTATES MONTH XX, XXXX