Grounding Audit Report | Interstates

Drawing E08-04 (Continued) Test Points

Area

Point

Equipment Tested A-2A Lighting Panel

Test Value (Ohms)

Grounded Circuit Used

Boiler House Area (Area 15) Boiler House Area (Area 15) Boiler House Area (Area 15) Boiler House Area (Area 15) Boiler House Area (Area 15) Boiler House Area (Area 15) Boiler House Area (Area 15) Boiler House Area (Area 15) Boiler House Area (Area 15) Boiler House Area (Area 15) Boiler House Area (Area 15) Boiler House Area (Area 15) Boiler House Area (Area 15) Boiler House Area (Area 15) Boiler House Area (Area 15) Boiler House Area (Area 15)

56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90

0.34 0.30 0.26 0.32 0.40 0.83 0.28 0.50 0.29 0.50 0.30 0.38 0.28 0.44 0.32 0.33

A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A A2 Circuit Whip 27 Recept, CB# N/A

A2 Lighting Panel

XFMR

Lighting Panel A-1

Junction Box

XFMR

Boiler Fan Decay

Water Lines (Pipes)

Weld Receptacle

Boiler Fan Disconnect

Boiler Fan Motor

PLC Cabinet

Monitoring Solutions

XFMR

Tank

Valves

Cooling Area (Area 16) Cooling Area (Area 16) Cooling Area (Area 16) Vac Pan Area (Area 18) Vac Pan Area (Area 18) Vac Pan Area (Area 18) Vac Pan Area (Area 18) Vac Pan Area (Area 18) Vac Pan Area (Area 18) Vac Pan Area (Area 18) Vac Pan Area (Area 18) Vac Pan Area (Area 18) Vac Pan Area (Area 18) Vac Pan Area (Area 18) Vac Pan Area (Area 18) Vac Pan Area (Area 18) Vac Pan Area (Area 18) Vac Pan Area (Area 18) Vac Pan Area (Area 18)

50K Tank 50K Tank 50K Tank

0.41

N/A N/A N/A

119.00 365.00

Reclaim Pump Motor

0.49 0.67 0.39 0.49 1.71 0.30 0.32 0.35 0.27 0.58 0.27 2.10 0.47 9.50 1.36 1.41

Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A Unknown Panel, CB# N/A

Reclaim Pump Disconnect Condensate Pressure Pump

Vac Pump

#4 Purge Pump

#4 Exhauster Motor

#4 Condensate Motor Evaporator Feed Motor

#3 Exhauster #2 Exhauster #1 Exhauster

Slurry Pump Motor

Screw Motor

Filter Wheel Motor

3rd Floor Lighting Panel 1 3rd Floor Lighting Panel 2

CLIENT NAME, FACILITY LOCATION GROUNDING REPORT

Page 14 of 23

INTERSTATES MONTH XX, XXXX

Powered by