SMITHFIELD Project: Carroll, IA Arc Flash Study CARROLL, IA ARC FLASH STUDY
DAPPER Fault Analysis Input Report (English)
Utilities
Contribution From Name
Bus Name
In/Out Service
Nominal Voltage
-------- Contribution Data --------
PU (100 MVA Base) R PU X PU
Duty Units
X/R
3P:
Pos: Zero:
100 UTIL [MAIN UTIL]
BUS-0193
In
12,470
3,486
Amps
3.12
0.405 1.265
0.928
2.461
SLG:
2,628
Amps
2.87
Motors
# of Motors
Total Rated HP
Motor Group
--------- Contribution Data --------
Contribution From Name
In/Out Service
Nominal Voltage
PU (100 MVA Base) R PU X PU
Base kVA
Xd"
X/R
100 MTR [300HP FES COMP
1
300.00
No
In
480
300.81 0.1507 4.90 10.229 50.111
110 MTR [PUMP CHILL H20
1
25.00
No
In
480
25.07 0.1531 10.00 61.066 610.689
120 MTR [AMFEC]
1
50.00
No
In
480
50.13 0.1531 10.00 30.533 305.345
120 MTR [AMMONIA COMP #
1
75.00
No
In
480
75.20 0.1531 10.00 20.355 203.563
120 MTR [AMMONIA COMP #
1
125.00
No
In
480
125.34 0.1531 10.00 12.213 122.138
120 MTR [AMMONIA COMP #
1
75.00
No
In
480
75.20 0.1531 10.00 20.355 203.563
130 MTR [AIR COMP 2]
1
75.00
No
In
480
75.20 0.1531 10.00 20.355 203.563
130 MTR [AIR COMP 3]
1
60.00
No
In
480
60.16 0.1531 10.00 25.444 254.454
130 MTR [AIR COMP 5]
1
75.00
No
In
480
75.20 0.1531 10.00 20.355 203.563
130 MTR [AMONIA UNIT 6]
1
125.00
No
In
480
125.34 0.1531 10.00 12.213 122.138
130 MTR [AMONIA UNIT 7
1
125.00
No
In
480
125.34 0.1531 10.00 12.213 122.138
Cables
Cable Name
From Bus To Bus
Qty /Ph
Length Feet
------ Cable Description ------ Size Cond. Type Duct Type Insul
Per Unit (100 MVA Base) R pu jX pu
Pos:
100 CBL [300HP FES COMP]
100 MCC [REFRIGERATION 100 ENC [300HP FES COMP] 100 SWBD [MAIN SWBD] 100 DISC [CAP DISC] 100 MCC [REFRIGERATION 100 ENC [CONDENSOR
2
50
4/0
Copper
Magnetic
PVC
0.6944 0.5393 1.3281 2.1886
Zero:
Pos:
100 CBL [CAP DISC]
1
10
3/0
Copper
Non-Magnetic
PVC
0.3325 0.1801 0.4579 0.5282
Zero:
Pos:
100 CBL [CONDENSOR NO 2
1
8
2
Copper
Magnetic
PVC
0.7014 0.2031 0.5000 2.2104
Zero:
1
SITE NAME ARC FLASH STUDY
Page 61 of 77
INTERSTATES DATE
Powered by FlippingBook