130-01 PANEL 2

130 PNL [ PANEL 2] PANEL 2 1200 A 480 V 18 kASCR

130 CB [S. CRYOVACPMP #1] Frame/Rating 60A Sensor/Trip60 A Plug 60 A InterruptingRating 18 kA

130 CB [AMONIAUNIT 6] Frame/Rating 400 A Sensor/Tr ip400A Plug 400A InterruptingRating 30 kA

130CB [XFMR PNL RM] Frame/Rating 150 A Sensor/Tr ip125A Plug 125A InterruptingRating 25 kA

130 CBL [S. CRYOVAC PMP#1] Magnetic 6 AWG 3-1/C+G QtyPerPhase 1 200.0 ft

130 DCBL [AMONIA UNIT 6] Magnetic 3/0 AWG 3-1/C+G QtyPerPhase 2 0.1 ft

130CBL [XFMR PNLRM] Magnetic 1 AWG 3-1/C+G QtyPerPhase 1 25.0 ft

P

130 ENC [S. CRYOVAC PMP #1] S. CRYOVAC PMP #1 60 A 480 V 10 kASCR

130XFMR [XFMR PNL RM] 112.5 kVA

S

480 V 208 V Z% 5.00 %

NEC VIOLATION

130 CBL [AMONIAUNIT 6] Magnetic 3/0 AWG 3-1/C+G QtyPerPhase 1 100.0 ft

130 CBL [AMONIA UNIT 7 VFD] Magnetic 3/0 AWG 3-1/C+G QtyPerPhase 1 100.0 ft

130 CBL [OFFI CE L GTS DISC] Magnetic 2 AWG 4-1/C+G QtyPerPhase 1 10.0 ft

130 CBL [S. SHOP TEST DISC] Magnetic 2 AWG 4-1/C+G QtyPerPhase 1 10.0 ft

130 CBL [S. CRYOVAC DISC] Magnetic 2 AWG 4-1/C+G QtyPerPhase 1 8.0 ft

130 CBL [PANEL 7 DISC] Magnetic 1/0 AWG 4-1/C+G QtyPerPhase 1 5.0 ft

130CBL [N. CRYOVAC DISC] Magnetic 2 AWG 4-1/C+G QtyPerPhase 1 8.0 ft

130 CBL [FRONT OFFICE DISC] Magnetic 2 AWG 4-1/C+G QtyPerPhase 1 10.0 ft

130 ENC [AMONIAUNIT6] AMONIA UNIT6

130 ENC [AMONIA UNIT7 VFD] AMONIAUNIT7 VFD

130DISC [OFFICE LGTSDISC] OFFICE LGTSDISC

130 DISC [S. SHOP TEST DISC] S. SHOP TEST STATION DI SC

130 DISC [S. CRYOVAC DISC] S. CRYOVAC DISC

130 DISC [PANEL 7 DISC] PANEL 7 DISC

130 DISC [N. CRYOVAC DI SC] N. CRYOVAC DISC

130 DISC [FRONT OFFICE DISC] FRONT OFFICE PNL DISC

250 A 480 V 10 kASCR

200 A 480 V 10 kASCR

100 A 208 V 100 kASCR

100 A 208 V 100 kASCR

100 A 208 V 100 kASCR

200 A 208 V 100 kASCR

100 A 208 V 100 kASCR

100 A 208 V 100 kASCR

130 MTR [AMONIAUNIT 6] 125 hp NumMotors 1 Group < 50hp 0

130 VFD [AMONIA UNIT 7 VFD]

130FUSE [OFFICE LGTSPNL] Frame/Rating 80A Sensor/Tr ip80 A InterruptingRating 200 kA

130 FUSE [S. SHOP TEST DISC] Frame/Rating 100 A Sensor/Tr ip100A InterruptingRating 200 kA

130 FUSE [S. CRYOVAC DISC] Frame/Rating 80A Sensor/Tr ip80 A InterruptingRating 200 kA

130 FUSE [PANEL 7] Frame/Rating 125 A Sensor/Tr ip125A InterruptingRating 200 kA

130 FUSE [N. CRYOVAC DI SC] Frame/Rating 80A Sensor/Tr ip80 A InterruptingRating 200 kA

130 FUSE [FRONT OFFICE PNL] Frame/Rating 100 A Sensor/Tr ip100A InterruptingRating 200 kA

130 MTR [AMONIA UNIT 7 VFD] 125 hp NumMotors 1 Group < 50hp 0

130 CBL [OFFI CE L GTS PNL] Magnetic 2 AWG 4-1/C+G QtyPerPhase 1 150.0 ft

130 CBL [PANEL 7] Magnetic 1/0 AWG 4-1/C+G QtyPerPhase 1 40.0 ft

130 CBL [FRONT OFFICE PNL ] Magnetic 2 AWG 4-1/C+G QtyPerPhase 1 170.0 ft

130 PNL [ OF FICE LGTS PNL] OFFICE LGTSPNL

130 PNL [PANEL 7] PANEL 7

130 PNL [FRONT OFFICE PNL] FRONTOFFICE PNL

100 A 208 V 10 kASCR

225 A 208 V 10 kASCR

100 A 208 V 10 kASCR

130 CB [PANEL 6] Frame/Rating 100 A Sensor/Tr ip100A Plug 100A InterruptingRating 10 kA

130 CB [PANEL 5] Frame/Rating 100 A Sensor/Tr ip100A Plug 100A InterruptingRating 10 kA

130 CBL [PANEL 6] Magnetic 2 AWG 4-1/C+G QtyPerPhase 1 5.0 ft

130 CBL [PANEL 5] Magnetic 2 AWG 4-1/C+G QtyPerPhase 1 5.0 ft

130 PNL [PANEL 6] PANEL 6

130 PNL [PANEL 5] PANEL 5

100 A 208 V 10 kASCR

100 A 208 V 10 kASCR

SMITHFIELD CARROLL, IA

130-02 PANEL 2 CONT

Base Project

ARC FLASH STUDY

October 4, 2022

Powered by