Table 4: Protective Device Settings Report

Name/Type

Description BUSSMANN

Frame/Sensor/Plug Settings

120 FUSE [EAST MULE XFMR]

40A FRS-R, 600V Class RK5 40A

120 FUSE [WEST MULE XFMR]

BUSSMANN 40A FRS-R, 600V Class RK5 40A

130 FUSE [FRONT OFFICE PNL]

BUSSMANN

100A 100A

FRS, 600V Class K5

130 FUSE [N. CRYOVAC DISC]

BUSSMANN 80A FRN-R, 250V Class RK5 80A

130 FUSE [OFFICE LGTS PNL]

BUSSMANN 80A FRN-R, 250V Class RK5 80A

130 FUSE [PANEL 7]

BUSSMANN 125A FRN-R, 250V Class RK5 125A

130 FUSE [S. CRYOVAC DISC]

BUSSMANN 80A FRN-R, 250V Class RK5 80A

130 FUSE [S. SHOP TEST DISC]

BUSSMANN

100A 100A

FRS, 600V Class K5

140 FUSE [LUNCH RM PNL]

BUSSMANN 125A FRN-R, 250V Class RK5 125A

SITE NAME ARC FLASH STUDY

Page 28 of 77