Arc Flash Report | Interstates

Table 4: Protective Device Settings Report

Name/Type

Description SQUARE D Powerpact HD

Frame/Sensor/Plug Settings

130 CB [AIR COMP 3]

125A 125A 125A 150A 150A 150A

Fixed

Thermal Magnetic

130 CB [AIR COMP 5]

SQUARE D

Phase

Thermal Magnetic

KA

Thermal Curve INST HI (1500A)

Recommended

Thermal Curve INST 2 (964.5A)

130 CB [AIR DRYER]

SQUARE D

20A 20A 20A

Fixed

Thermal Magnetic

FA

130 CB [AMONIA UNIT 6]

SQUARE D

400A 400A 400A

Thermal Curve INST HI (4000A)

Thermal Magnetic

LA

130 CB [BOILER #2 NORTH]

SQUARE D

30A 30A 30A 40A 40A 40A

Fixed

Thermal Magnetic

FH

130 CB [BOILER H20 PMP DISC]

SQUARE D

Fixed

Thermal Magnetic

FA

130 CB [BOILER RM PNL]

SQUARE D

400A 400A 400A

Phase

Thermal Magnetic

LA

Thermal Curve INST HI (4000A)

Recommended

Thermal Curve INST 2 (2564A)

130 CB [DUMPER N CLIPPER TIE]

SQUARE D

15A 15A 15A 15A 15A 15A 15A 15A 15A 15A 15A 15A 40A 40A 40A 15A 15A 15A

Fixed

Thermal Magnetic

FA

130 CB [E PROCESS WALL EVAP]

SQUARE D

Fixed

Thermal Magnetic

FA

130 CB [ELEVATOR] Thermal Magnetic

SQUARE D

Fixed

FA

130 CB [GRIND MIX AUGER]

SQUARE D

Fixed

Thermal Magnetic

FA

130 CB [MEAT INSPECT CNVRY]

SQUARE D

Fixed

Thermal Magnetic

FA

130 CB [N. OPTI VACUUM PMP]

SQUARE D

Fixed

Thermal Magnetic

FA

130 CB [PANEL 2] Thermal Magnetic

SQUARE D

1200A 1200A 1200A

Thermal Curve INST HI (9120A)

PA

SITE NAME ARC FLASH STUDY

Page 25 of 77

INTERSTATES DATE

Powered by