Table 4: Protective Device Settings Report
Name/Type
Description SQUARE D Powerpact HD
Frame/Sensor/Plug Settings
130 CB [AIR COMP 3]
125A 125A 125A 150A 150A 150A
Fixed
Thermal Magnetic
130 CB [AIR COMP 5]
SQUARE D
Phase
Thermal Magnetic
KA
Thermal Curve INST HI (1500A)
Recommended
Thermal Curve INST 2 (964.5A)
130 CB [AIR DRYER]
SQUARE D
20A 20A 20A
Fixed
Thermal Magnetic
FA
130 CB [AMONIA UNIT 6]
SQUARE D
400A 400A 400A
Thermal Curve INST HI (4000A)
Thermal Magnetic
LA
130 CB [BOILER #2 NORTH]
SQUARE D
30A 30A 30A 40A 40A 40A
Fixed
Thermal Magnetic
FH
130 CB [BOILER H20 PMP DISC]
SQUARE D
Fixed
Thermal Magnetic
FA
130 CB [BOILER RM PNL]
SQUARE D
400A 400A 400A
Phase
Thermal Magnetic
LA
Thermal Curve INST HI (4000A)
Recommended
Thermal Curve INST 2 (2564A)
130 CB [DUMPER N CLIPPER TIE]
SQUARE D
15A 15A 15A 15A 15A 15A 15A 15A 15A 15A 15A 15A 40A 40A 40A 15A 15A 15A
Fixed
Thermal Magnetic
FA
130 CB [E PROCESS WALL EVAP]
SQUARE D
Fixed
Thermal Magnetic
FA
130 CB [ELEVATOR] Thermal Magnetic
SQUARE D
Fixed
FA
130 CB [GRIND MIX AUGER]
SQUARE D
Fixed
Thermal Magnetic
FA
130 CB [MEAT INSPECT CNVRY]
SQUARE D
Fixed
Thermal Magnetic
FA
130 CB [N. OPTI VACUUM PMP]
SQUARE D
Fixed
Thermal Magnetic
FA
130 CB [PANEL 2] Thermal Magnetic
SQUARE D
1200A 1200A 1200A
Thermal Curve INST HI (9120A)
PA
SITE NAME ARC FLASH STUDY
Page 25 of 77
INTERSTATES DATE
Powered by FlippingBook