Table 4: Protective Device Settings Report
Name/Type
Description
Frame/Sensor/Plug Settings
100 CB [300HP FES COMP]
SIEMENS
600A 600A 600A
Thermal Curve (Fixed) INST (LO-HI) 2 (3430A)
Thermal Magnetic
HLXD6 Sentron
100 CB [INJECTOR #1 COOLING]
SQUARE D
15A 15A 15A
Fixed
Thermal Magnetic
FA
100 CB [PANEL ABC XFMR]
CUTLER-HAMMER
110A 110A 110A
Thermal Curve
Thermal Magnetic
EGB, 3-4 Poles
Magnetic (Fixed) Fixed (1155A)
100 CB [PANEL E XFMR]
SQUARE D
30A 30A 30A
Fixed
Thermal Magnetic
FA
100 CB [REFRIGERATION MCC]
SQUARE D
1000A 1000A 1000A
Thermal Curve INST HI (9000A)
Thermal Magnetic
PA
100 MCB [PANEL A] Thermal Magnetic
CUTLER-HAMMER
225A 150A 150A 225A 150A 150A
Fixed
CA
100 MCB [PANEL B] Thermal Magnetic
CUTLER-HAMMER
Fixed
CA
100 MCB [PANEL E] Thermal Magnetic
EATON/CUTLER-HAMMER 60A
Fixed
BAB, 2-Pole
60A 60A
110 CB [CHILL H20 BILGE PMP]
SQUARE D
40A 40A 40A 15A 15A 15A
Fixed
Thermal Magnetic
FA
110 CB [CHILL RM PMP STR]
SQUARE D
Fixed
Thermal Magnetic
FA
110 CB [CHILL ROOM PNL]
SQUARE D
400A 400A 400A
Thermal Curve INST HI (4000A)
Thermal Magnetic
LA
110 CB [CHILLER RM XFMR]
SQUARE D
50A 50A 50A 30A 30A 30A
Fixed
Thermal Magnetic
FA
110 CB [FLR LIFT HYD STR]
SQUARE D
Fixed
Thermal Magnetic
FA
110 CB [GRIND MIX/WIELER]
SQUARE D
150A 150A 150A
Thermal Curve INST HI (1500A)
Thermal Magnetic
KA
110 CB [GRND/MIX HYD DUMP]
SQUARE D
40A 40A 40A 60A 60A 60A
Fixed
Thermal Magnetic
FA
110 CB [MARLEN PMP]
SQUARE D
Fixed
Thermal Magnetic
FA
SITE NAME ARC FLASH STUDY
Page 22 of 77
INTERSTATES DATE
Powered by FlippingBook