Arc Flash Report | Interstates

Table 4: Protective Device Settings Report

Name/Type

Description

Frame/Sensor/Plug Settings

100 CB [300HP FES COMP]

SIEMENS

600A 600A 600A

Thermal Curve (Fixed) INST (LO-HI) 2 (3430A)

Thermal Magnetic

HLXD6 Sentron

100 CB [INJECTOR #1 COOLING]

SQUARE D

15A 15A 15A

Fixed

Thermal Magnetic

FA

100 CB [PANEL ABC XFMR]

CUTLER-HAMMER

110A 110A 110A

Thermal Curve

Thermal Magnetic

EGB, 3-4 Poles

Magnetic (Fixed) Fixed (1155A)

100 CB [PANEL E XFMR]

SQUARE D

30A 30A 30A

Fixed

Thermal Magnetic

FA

100 CB [REFRIGERATION MCC]

SQUARE D

1000A 1000A 1000A

Thermal Curve INST HI (9000A)

Thermal Magnetic

PA

100 MCB [PANEL A] Thermal Magnetic

CUTLER-HAMMER

225A 150A 150A 225A 150A 150A

Fixed

CA

100 MCB [PANEL B] Thermal Magnetic

CUTLER-HAMMER

Fixed

CA

100 MCB [PANEL E] Thermal Magnetic

EATON/CUTLER-HAMMER 60A

Fixed

BAB, 2-Pole

60A 60A

110 CB [CHILL H20 BILGE PMP]

SQUARE D

40A 40A 40A 15A 15A 15A

Fixed

Thermal Magnetic

FA

110 CB [CHILL RM PMP STR]

SQUARE D

Fixed

Thermal Magnetic

FA

110 CB [CHILL ROOM PNL]

SQUARE D

400A 400A 400A

Thermal Curve INST HI (4000A)

Thermal Magnetic

LA

110 CB [CHILLER RM XFMR]

SQUARE D

50A 50A 50A 30A 30A 30A

Fixed

Thermal Magnetic

FA

110 CB [FLR LIFT HYD STR]

SQUARE D

Fixed

Thermal Magnetic

FA

110 CB [GRIND MIX/WIELER]

SQUARE D

150A 150A 150A

Thermal Curve INST HI (1500A)

Thermal Magnetic

KA

110 CB [GRND/MIX HYD DUMP]

SQUARE D

40A 40A 40A 60A 60A 60A

Fixed

Thermal Magnetic

FA

110 CB [MARLEN PMP]

SQUARE D

Fixed

Thermal Magnetic

FA

SITE NAME ARC FLASH STUDY