Arc Flash Report | Interstates

Table 2: Arc Flash Evaluation Report

Bus Name

Protective

Bus

Bus Prot Dev Prot Dev Trip/

Arc

Electrode

Working Incident

PPE Level

Label #

Device Name

kV Bolted Bolted Arcing Delay Flash Configuartion Distance Energy

Fault

Fault

Fault

Time Boundary

(cal/cm2)

(kA)

(kA)

(kA)

(sec.)

140 ENC [TUMBLER DUMP] (TUMBLER DUMP)

140 CB [DUMP TAP]

0.480 3.86

3.86

3.00 0.0167 5"

VCBB

1' 6"

0.12 Level 0

# 0111

140 ENC [USDA FIRST BELT] (USDA FIRST BELT)

140 CB [LOG/USDA TAP]

0.480 4.46

4.46

3.47 0.0167 5"

VCBB

1' 6"

0.14 Level 0

# 0112

140 ENC [WEILER AUGER FEED] (WEILER AUGER FEED)

140 CB [PICKLE/WEILER TAP]

0.480 3.86

3.86

3.00 0.0167 5"

VCBB

1' 6"

0.12 Level 0

# 0113

140 ENC [WOLFTEC INJECTOR] (WOLFTEC INJECTOR)

140 CB [WOLFTEC INJECTOR]

0.480 1.76

1.76

1.36 0.0175 3"

VCBB

1' 6"

0.05 Level 0

# 0114

140 PNL [LUNCH RM PNL] (LUNCH RM PNL)

140 FUSE [LUNCH RM PNL]

0.208 3.38

3.38

1.21 0.6961 1' 11"

VCBB

1' 6"

1.80 Level 1

# 0115

140 PNL [PANEL 3] (PANEL 3)

130 CB [PANEL 2]

0.480 27.07 25.18 20.44 0.0502 2' 8"

VCBB

1' 6"

3.43 Level 1

# 0116

140 PNL [UPSTAIRS LV PNL] (UPSTAIRS LV PNL)

140 FUSE [LUNCH RM PNL]

0.208 3.38

3.38

1.21 0.6961 1' 11"

VCBB

1' 6"

1.80 Level 1

# 0117

140 STR [PICKLE MAS STR] (PICKLE PMP MASCERATOR STR)

140 CB [PICKLE/WEILER TAP]

0.480 4.46

4.46

3.47 0.0167 5"

VCBB

1' 6"

0.14 Level 0

# 0118

140 STR [PICKLE PMP STR] (PICKLE PMP BRINE CHILLER STR)

140 CB [PICKLE PMP STR]

0.480 3.87

3.87

3.01 0.0167 5"

VCBB

1' 6"

0.12 Level 0

# 0119

140 VFD [PICKLE PMP VFD] (PICKLE PMP BRINE CHILLER VFD)

140 CB [PICKLE PMP STR]

0.480 3.58

3.58

2.78 0.0167 5"

VCBB

1' 6"

0.11 Level 0

# 0120

140 VFD [WEILER TAKEAWAY VFD] (WEILER AUGER TAKEAWAY VFD) 140 CB [WEILER TAP]

0.480 2.14

2.14

1.65 0.0167 3"

VCBB

1' 6"

0.06 Level 0

# 0121

SITE NAME ARC FLASH STUDY

Page 13 of 77

INTERSTATES DATE

Powered by